· temperature measurement
· Thermistor, NI and PT sensing elements to fit your system
· Simple and secure installation
· Wide range of temperature probes
· Outside air temperature measurements for summer winter compensation, energy optimization and economizer.
· Frost protection control of outside air dampers
The sensor measures the temperature by use of a NTC, PT, or NI-sensing element. The sensing element is either a glass packed thermistor with a negative temperature coefficient, a platinum film or a nickel thin layer based probe. Its resistance changes according to the temperature. The change follows a specified curve. Contact our sales department for curves not yet listed below.
Item Name | Item Code | Probe | Definition | Comments |
SPD-Tn3 | 40-20 0058 | NTC 3kΩ at 25°C | B25/50 3935 | |
SPD-Tn10 | 40-20 0059 | NTC 10kΩ at 25°C | B25/50 3935 | Vector Standard |
SPD-Tn11 | 40-20 0060 | NTC 10kΩ at 25°C | B25/50 3630 | |
SPD-Tn20 | 40-20 0061 | NTC 20kΩ at 25°C | B25/50 4200 | |
SPD-Tn100 | 40-20 0062 | NTC 100kΩ at 25°C | B25/50 4200 | |
SPD-Tp1 | 40-20 0063 | PT100 | EN60751 | |
SPD-Tp2 | 40-20 0064 | PT1000 | EN60751 | |
SPD-Tk5 | 40-20 0065 | NI1000 | 5000 ppm/K | |
SPD-T1 | 40-20 0065 | 4-20mA或0-10V |
Outside air probes must be installed on a flat vertical surface protected from direct sunlight and rain.
· The cable gland must face downwards.
· To install the sensor, remove cover
· Place seal and washer below the long mounting screw. Securely fix it to wall.
· Thread wires through cable gland or conduit connector
· Connect the wires according to the wiring diagram to the measuring circuit in the cover:
o The Thermistors require two conductors; normally 18ga unshielded twisted pair.
o The PT1000 sensors come with each two terminal connectors in order to connect up to four conductors for compensating conductor resistance.
· Tighten cable gland
· Assemble the cover with the base plate. Make sure the seal in the seal grove of the cover is not damaged and in place.
· Tighten the four screws of the cover with moderate torque to complete the installation.
Sensing Probe | Thermistor: | NTC,PT100,T1 |
Platinum-Film: | PT according EN 60751 | |
Nickel Thin Layer: | 1000 V at 0°C, 5000 ppm/K | |
Connection | Terminal Connectors | For wire 0.34…2.5 mm2 (AWG 24…12) |
Environment | Operation | To IEC 721-3-3 |
Transport & Storage | To IEC 721-3-2 and IEC 721-3-1 | |
Standards |
|
|
Product standards |
| |
Degree of Protection | IP65 to EN 60 529 | |
Safety Class | III (IEC 60536) | |
Housing | Material | Fire proof PC + ABS plastic |
Dimensions Cover: (H x W x D) | 33 x 60 x 50 mm (1.3 x 2.4 x 2 in) | |
Weight (including package) | 80 g (2.8 oz) |