成人午夜亚洲精品无码区,中文字幕人妻熟在线影院,亚洲精品久久久久久中文字幕,欧美牲交a欧美牲交aⅴ一,亚洲午夜精品a片一区二区小蝌蚪

Two-wire PT100/PT1000 temperature transmitter

Detail

Back


SPD-T
 Temperature Sensor

Features

·           temperature measurement

·          Thermistor, NI and PT sensing elements to fit your system

·          Simple and secure installation

·         Wide range of temperature probes

Applications

·          Outside air temperature measurements for summer winter compensation, energy optimization and economizer.

·         Frost protection control of outside air dampers

Temperature Sensor

The sensor measures the temperature by use of a NTC, PT, or NI-sensing element. The sensing element is either a glass packed thermistor with a negative temperature coefficient, a platinum film or a nickel thin layer based probe. Its resistance changes according to the temperature. The change follows a specified curve. Contact our sales department for curves not yet listed below.

Ordering

Item Name

Item Code

Probe

Definition

Comments

SPD-Tn3

40-20 0058

NTC 3kΩ at 25°C

 B25/50 3935


SPD-Tn10

40-20 0059

NTC 10kΩ at 25°C

 B25/50 3935

Vector Standard

SPD-Tn11

40-20 0060

NTC 10kΩ at 25°C

 B25/50 3630


SPD-Tn20

40-20 0061

NTC 20kΩ at 25°C

 B25/50 4200


SPD-Tn100

40-20 0062

NTC 100kΩ at 25°C

 B25/50 4200


SPD-Tp1

40-20 0063

PT100

EN60751


SPD-Tp2

40-20 0064

PT1000

EN60751


SPD-Tk5

40-20 0065

NI1000

5000 ppm/K


SPD-T1

40-20 0065

4-20mA0-10V



Installation

Outside air probes must be installed on a flat vertical surface protected from direct sunlight and rain.

·          The cable gland must face downwards.

·          To install the sensor, remove cover

·          Place seal and washer below the long mounting screw. Securely fix it to wall.

·          Thread wires through cable gland or conduit connector

·          Connect the wires according to the wiring diagram to the measuring circuit in the cover:

o    The Thermistors require two conductors; normally 18ga unshielded twisted pair.

o    The PT1000 sensors come with each two terminal connectors in order to connect up to four conductors for compensating conductor resistance.

·          Tighten cable gland

·          Assemble the cover with the base plate. Make sure the seal in the seal grove of the cover is not damaged and in place.

·          Tighten the four screws of the cover with moderate torque to complete the installation.


Technical Specification

Sensing Probe

Thermistor:
Accuracy:  
-40…0°C:
                   0…50°C:
                   50…200°C:

NTC,PT100,T1
0.5 K
0.2 K
0.5 K


Platinum-Film:
Accuracy

PT according EN 60751
EN 60751, Class B


Nickel Thin Layer:
Accuracy

1000 V at 0°C, 5000 ppm/K
DIN 43760

Connection

Terminal Connectors

For wire 0.34…2.5 mm2 (AWG 24…12)

Environment

Operation
Climatic Conditions
Temperature
Humidity

To IEC 721-3-3
class 3 K5
-40…100°C (-40…212°F)
<95% R.H. non-condensing


Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions

To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-40…100°C (-40…212°F)
<95% R.H. non-condensing
class 2M2

Standards

          conform according to
EMC Standard 89/336/EEC
EMEI Standard 73/23/EEC


EN 61 000-6-1/ EN 61 000-6-3

Product standards
Automatic electrical controls for household and similar use
Special requirement on temperature dependent controls


EN 60 730 –1

EN 60 730 – 2 - 9

Degree of Protection

IP65 to EN 60 529

Safety Class

III (IEC 60536)

Housing

Material

Fire proof PC + ABS plastic


Dimensions         Cover: (H x W x D)

33 x 60 x 50 mm (1.3 x 2.4 x 2 in)


Weight (including package)

80 g (2.8 oz)