The fan coil is an important equipment for adjusting the temperature and humidity in the cabin of a ship. Usually the fan coil is composed of tube-fin heat exchanger, blower, water pan, air filter, frame, etc.
?Feature: small volume, light weight and low noise
?Cooling capacity. 2kW ~ 13kW
?Cooling medium: chilled water
?Heating medium: hot water
?Control: temp auto regulation, three steps or stepless regulation of air flow
Model number project | FCU- | FCU- | FCU- | FCU- | FCU- | FCU- | FCU- | FCU- | FCU- | |
Rated air volume m3/h | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 | |
Rated cooling capacity(w) | 1800 | 2700 | 3600 | 4500 | 5400 | 7200 | 9000 | 10800 | 12600 | |
Rated heat(w) | 2700 | 4050 | 5400 | 6750 | 8100 | 10800 | 13500 | 16200 | 18900 | |
noise dB(A) | <40 | <42 | <44 | <46 | <47 | <48 | <50 | <52 | <54 | |
Water flow m3/h | 0.31 | 0.46 | 0.62 | 0.77 | 0.93 | 1.23 | 1.54 | 1.85 | 2.16 | |
Water pressure drop kPa | <30 | <30 | <30 | <30 | <40 | <40 | <40 | <40 | <50 | |
Piping | Inlet and Outlet | 1/2″ | 1/2″ | 1/2″ | 1/2″ | 1/2″ | 1/2″ | 1/2″ | 1/2″ | 1/2″ |
Effusion tube | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | |
power supply Ph/V/Hz | 1/220/50或1/220/60 | |||||||||
input power (w) | 44 | 59 | 72 | 87 | 108 | 156 | 174 | 212 | 253 | |
size (Length x width x height) kg | Vertical surface mount | 910x545x265 | 1030x545x265 | 1150x545x265 | 1400x545x265 | 1515x545x265 | 1630x545x265 | 1750x545x265 | 1990x545x265 | 2230x545x265 |
Horizontal concealed installation | 730x480x250 | 830x480x250 | 930x480x250 | 1150x480x250 | 1350x480x250 | 1450x480x250 | 1550x480x250 | 1750x480x250 | 2050x480x250 | |
Cassette surface mount | 650x650x290 | 650x650x290 | 650x650x290 | 850x850x320 | 850x850x320 | 850x850x320 | 1050x1050x320 | 1050x1050x320 | 1050x1050x320 | |
Cabinet type surface installation | 480x260x1500 | 480x260x1500 | 480x260x1500 | 600x300x1500 | 600x300x1500 | 600x300x1500 | 600x500x1750 | 600x500x1750 | 600x500x1750 | |
weight | Vertical surface mount | 22 | 24 | 27 | 31 | 41 | 43 | 45 | 51 | 60 |
Horizontal concealed installation | 15 | 17 | 19 | 22 | 30 | 31 | 33 | 37 | 46 | |
Cassette surface mount | 28 | 28 | 28 | 37 | 37 | 37 | 60 | 60 | 60 | |
Cabinet type surface installation | 60 | 60 | 60 | 90 | 90 | 90 | 110 | 110 | 110 | |
Note: Cooling capacity measurement conditions: dry bulb temperature 27°C, wet bulb temperature 19.5°C, inlet water temperature 7°C, inlet and outlet water temperature difference 5K Heat measurement conditions: dry bulb temperature 21℃, inlet water temperature 60℃; water flow is the same as cooling conditions | ||||||||||